Technical Data Of Modulating Dual Fuel Burner:
Model | GI/EMME 1400 | GI/EMME 2000 | GI/EMME 3000 | GI/EMME 4500 | ||
Burner operation mode | Modulating (with regulator and probes accessories) or two stage progressive | |||||
Modulation ratio at max. output | 3:1 | |||||
Servomotor | run time | type | SQM 10.16502 | |||
s | 42 | |||||
Heat output | kW | 407/820-1540 | 581/1163-2325 | 872/1744-3488 | 1163/2350-4650 | |
Mcal/h | 350/705-1324 | 500/1000-2000 | 750/1500-3000 | 1000/2021-4000 | ||
Working temperature | oC min./max. | 0/40 | ||||
Fuel / Air Data | ||||||
Oil | Net calorific value | kWh/kg | 11,8 | |||
Viscosity | mm2/s ( cSt) | 4-6 (at 20oC) | ||||
Delivery | kg/h | 34/69-130 | 49/99-197 | 74/148-296 | 99/199-394 | |
Pump | type | TA2 | TA3 | TA4 | TA5 | |
Delivery | kg/h | 336 (at 25 bar) | 546 (at 25 bar) | 706 (at 25 bar) | 1008 (at 25 bar) | |
Atomised pressure | bar | 25 | ||||
Fuel temperature | max oC | 60 | ||||
Fuel preheater | NO | |||||
G20 | Net calorific value | kWh/Nm3 | 10 | |||
Density | kg/Nm3 | 0,71 | ||||
Gas delivery | Nm3/h | 41/82-154 | 58/116-232,5 | 87/174-349 | 116/235-465 | |
G25 | Net calorific value | kWh/Nm3 | 8,6 | |||
Density | kg/Nm3 | 0,78 | ||||
Gas delivery | Nm3/h | 47/95-179 | 68/135-270 | 101/203-406 | 135/273-541 | |
LPG | Net calorific value | kWh/Nm3 | 25,8 | |||
Density | kg/Nm3 | 2,02 | ||||
Fan | type | Centrifugal with reverse curve blades | ||||
Air temperature | max oC | 60 | ||||
Electrical data | ||||||
Electrical supply | Ph / Hz / V | 3N/50/230-400 (+10%) | ||||
Auxiliary electrical supply | Ph / Hz / V | 1/50/230 (+10%) | ||||
Control box | type | LFL 1.333 | ||||
Total electrical power | kW | 5,1 | 6,1 | 12 | 15,5 | |
Auxiliary electrical power | kW | 1 | 1 | 1,5 | 2 | |
Heaters electrical power | kW | -- | ||||
Protection level | IP | 44 | ||||
Pump motor electrical power | kW | 1,1 | 1,1 | 1,5 | 1,5 | |
Rated pump motor current | A | 3 | 3 | 3,7 | 3,7 | |
Pump motor start up current | A | -- | ||||
Pump motor protection level | IP | 44 | ||||
Fan motor electrical power | kW | 3 | 4 | 9 | 12 | |
Rated fan motor current | A | 6,1 | 8 | 17 | 23 | |
Fan motor start up current | A | 44,5 | 64 | 124,1 | 158,7 | |
Fan motor protection level | IP | 44 | 44 | 44 | 55 | |
Ignition transformer | type | -- | ||||
V1- V2 | 230 V - 2 x 6 kV | |||||
I1 - I2 | 1,9 A - 35 mA | |||||
Operation | Intermittent (at least one stop every 24h) | |||||
Approval Emissions | ||||||
Sound pressure | dB(A) | 85,4 | 88 | 92 | 93,1 | |
Sound power | W | -- | ||||
Oil | CO emission | mg/kWh | < 50 | |||
Grade of smoke indicator | No Bacharach | < 1 | ||||
CxHy emission | mg/kWh | -- | ||||
NOx emission | mg/kWh | < 250 | ||||
G20 | CO emission | mg/kWh | < 100 | |||
NOx emission | mg/kWh | < 150 | ||||
Directive | 90/396 - 89/336 - 73/23 EEC | |||||
Conforming to | EN 267 - EN 676 | |||||
Certification | CE 0085AQ0712 | CE 0085AQ0712 | CE 0085AQ0712 | CE 0085AQ0712 | ||
DIN 5G830/97 M | DIN 5G831/97 M | DIN 5G832/97 M | DIN 5G833/97 M |